GBA Logo horizontal- lakesideca.info Facebook- lakesideca.info LinkedIn- lakesideca.info Email- lakesideca.info Pinterest- lakesideca.info Twitter- lakesideca.info Instagram- lakesideca.info YouTube Icon- lakesideca.info Navigation Search Icon- lakesideca.info Main Search Icon- lakesideca.info Video Play Icon- lakesideca.info Audio Play Icon- lakesideca.info Headphones Icon- lakesideca.info Plus Icon- lakesideca.info Minus Icon- lakesideca.info Check Icon- lakesideca.info Print Icon- lakesideca.info Picture icon- lakesideca.info Single Arrow Icon- lakesideca.info Double Arrow Icon- lakesideca.info Hamburger Icon- lakesideca.info TV Icon- lakesideca.info Close Icon- lakesideca.info Sorted- lakesideca.info Hamburger/Search Icon- lakesideca.info
Building Science

More Wingnut Testing of Basement Waterproofing

The difference between hydrostatic pressure and wicking

I tested different waterproofing compounds on the same four concrete block columns used in my first round of testing. I sprayed the interior of the top blocks on all four sides until the top block was saturated.
View Gallery 6 images

In the first round of Wingut testing of negative side waterproofing, I was pretty focused on how various interior basement waterproofing systems dealt with hydrostatic pressure. But in I conducted for a Wisconsin nonprofit called SeventhWave, I have gotten this question just about every time: “OK, so you need the crystalline waterproofing systems to deal with water under pressure. But what about basement walls and floors that see water that is not under pressure?”

That question got me thinking: could I use the same waterproofed concrete block columns and wet them in such a way that water would wick into the concrete by capillarity? This is liquid water that gets pulled into the masonry (concrete, block, brick, etc.) rather than liquid water that is pushed.

This test requires a spray bottle

As water runs down the untreated exterior wall of a foundation, the water gets pulled into untreated, porous masonry by wicking. If enough water is running down the exterior surface, the porous masonry can become saturated all the way to the interior surface.

The test method that I came up with turned out to be pretty simple: Rather than pouring water into the concrete columns, I simply sprayed the top blocks. The sprayed water (applied to the interior of the blocks) is just like water running down the exterior of the basement wall. (See the photo above, and the first image in the Gallery.)

When I sprayed the untreated block column, it took about 10 minutes of continuous spraying before the exterior surface of the top block showed signs of wetting. I then sprayed the column treated with UGL Drylok Extreme (see Image #2 in the Gallery).

You will have to trust me on this: there is no water being expressed on the exterior of the Drylok column. That frankly surprised me, so I continued wetting both columns for an additional 10 minutes: still no wicked water to the exterior of the Drylok column.

The Xypex column gets damp

I then pulled up the two crystalline waterproofed concrete block columns: the one treated with Xypex Concentrate and the one treated with Koster NB1 Grey. Repeating the spraying process, I got another surprise: the top block of the Xypex column showed wetting while the Koster column did not (see Images #3 and #4).

To be absolutely sure of these results, I repeated the spray water test for each column a week after the first test: the results were the same. The Drylok and Koster columns did not show any signs of wetting on the exterior, but both the untreated column and the Xypex column did show signs of wetting (see Images #5 and #6).

Interpret these results with caution

Conclusion? You know my caveats about this sort of “wingnut” testing: these are anecdotal reports; you should do your own testing using the materials in your basements: brick, block, or cast concrete. But my testing shows that while Drylok did not stop water under hydrostatic pressure, it did stop water from wicking past the waterproofing. Conversely, Xypex did stop water under hydrostatic pressure but not from wicking. Only the Koster waterproofing system resisted both hydrostatic pressure and wicking.

The only explanation I have for these results is that the priming and bonding emulsion elements of the Koster system — ones that I was specifically directed by Koster to apply to deal with the concrete block composition — are essential for full waterproofing results in CMU assemblies.

And these results suggest that if you are sure that your below-grade assemblies will never see hydrostatic pressure, maybe the non-crystalline Drylok will work. But remember: none of these systems are self-healing for future cracks, so the need to inspect (and possibly repair) these negative side waterproofing systems holds.

Note: The best way I can think of to improve on wingnut testing is for you to do testing of your own, and work with product manufacturers to explain the results and improve our real-world testing.

 

In addition to acting as GBA’s technical director, Peter Yost is the Vice President for Technical Services at in Brattleboro, Vermont. He has been building, researching, teaching, writing, and consulting on high-performance homes for more than twenty years. An experienced trainer and consultant, he’s been recognized as NAHB Educator of the Year. Do you have a building science puzzle? . You can also to get a free report on insulation, as well as regular posts from Peter.