Will Thick Cellulose Cause Your Ceiling to Sag?

musingsheader image

Will Thick Cellulose Cause Your Ceiling to Sag?

No — even very thick attic cellulose shouldn’t lead to a sagging drywall ceiling

Posted on Jan 12 2018 by Martin Holladay
prime

It’s fairly common for cold-climate builders to install a very thick layer of cellulose on an attic floor (that is, above the drywall ceiling of the floor below). Many green builders aim for a ceiling rated at R-60, R-70, or even R-100. When it comes installing cellulose, the usual advice is to “pile it on.”

Cellulose rated at R-60 is about 16 or 17 inches deep. Cellulose rated at R-100 is about 27 or 28 inches deep. That’s a lot of cellulose — so much, in fact, that some builders ask, “Is my drywall ceiling going to sag?”

Recommendations of drywall manufacturers

The biggest manufacturer of drywall in North America, U.S.G. Corporation, provides the following recommendation: “To prevent objectionable sag in new gypsum panel ceilings, the weight of overlaid unsupported insulation should not exceed: 1.3 psf for 1/2"-thick panels with frame spacing 24" o.c.; 2.4 psf for 1/2" panels on 16" o.c. framing (or 1/2" Sheetrock brand interior gypsum ceiling board, sag-resistant on 24" o.c. framing); 2.2 psf for 5/8" panels on 24" o.c. framing.”

These recommendations are summarized in the table below.

Readers will note that is table has columns for two types of cellulose: hammer-mill cellulose that settles to a density of 2.3 lbs/ft³, and fiberized cellulose that settles to a density of 1.5 lbs/ft³. The higher density cellulose was sold in the 1960s, ’70s, and ’80s. Newer types of cellulose developed in the early 1990s (so-called fiberized cellulose) have an installed density (in attic installations) of 1.5 lbs/ft³ (shown in the last column of the table).

Should these recommendations be followed?

Many green builders ignore these recommendations from U.S.G., and routinely exceed the recommended weight limits.

In a post on the Q&A pages of GBA, a reader named Jon Harrod noted, “We’ve loose-filled dozens of 24-inch-on-center attics to R-60 over a period of 10 years and can report zero issues related to the weight of the cellulose. This includes both new construction and retrofits with older, nailed sheetrock.”

Bill Hulstrunk, the former technical manager at National Fiber, a cellulose manufacturer, said, “We have never seen a sagging issue due to the weight of the cellulose installed above a ceiling. That may be because some of the weight of the cellulose is being redistributed onto the ceiling joists. We have blown very high R-values, up to R-100, and never had any issues with the ceiling sagging.”

Hultrunk’s speculation that the ceiling joists bear some of the weight of the cellulose makes sense. Clearly, not all of the cellulose weight bears on the drywall; once the cellulose has settled, it may act like brick veneer or a stone-and-mortar vaulted ceiling, with some of the weight of the upper layers of cellulose being transferred to the joists. If the cellulose is well consolidated, it could act (structurally speaking) as an arch; moreover, friction at the sides of the joists could also bear some of the cellulose's weight.

USG says, “No comment”

I recently contacted USG Corporation to find out whether their recommendations have changed. Veronica Feldmeier, whose job title at USG is PR Strategist, responded. Feldmeier wrote, “USG recommends 1/2" USG Sheetrock Brand UltraLight Panels and 1/2" USG Sheetrock Brand MH UltraLight Ceiling Panels UltraBase, which are specially formulated to support water-based spray texture paints and overlaid insulation with the same sag resistance as regular 5/8″ gypsum board. ... Due to their enhanced sag resistance, the panels are also recognized for installation with their long dimension oriented parallel to 24-inch OC ceiling framing, supporting insulation, and finished with a water-based, spray-texture ceiling finish.”

Feldmeier did not comment on USG's published weight limits, nor on Hulstrunk's theory that much of the weight of the cellulose insulation is transferred to the ceiling joists.

What causes drywall to sag?

The most common reason that drywall ceilings start to sag is that the ceiling gets damp. If you can keep your ceiling dry, sagging is unlikely.

Of course, 5/8" drywall (or one of the new sag-resistant 1/2" drywall products) is stiffer than ordinary 1/2" drywall.

If you are worried about drywall sagging — in spite of the evidence that such worries are baseless — you may want to install 1x3 or 1x4 strapping, 16 inches on center, on the underside of your ceiling joists before installing the drywall.

Martin Holladay’s previous blog: “Vermont Addresses the 20+5 Wall Problem — Sort Of.”


Tags: , , , , , ,

Image Credits:

  1. Michael Trolle / Lakesideca Advisor

1.
Jan 12, 2018 6:53 PM ET

Unreasonable Contractors
by Walter Ahlgrim

I could not get my insulation sub contractor to install beyond R38 unless I signed off that they were not liable if my ceiling drywall collapse, even if I signed they would not install over R49.

He claimed he had a ceiling drywall fall to the floor from the weight of the insulation they were in the process of installing. My guess is the thicker the insulation the more difficult it is to find the framing it stand on someone stepped on the drywall.

If you think about it from the contractor’s point of view why take the risk of going beyond USG’s recommendations if anything go wrong it is all on them.

The case could be made that installing more insulation than USG’s chart is a code violation as you are not following the manufactures instructions

Walt


2.
Jan 13, 2018 7:00 AM ET

Response to Walter Ahlgrim
by Martin Holladay

Walter,
Your point -- "The case could be made that installing more insulation than USG’s chart is a code violation as you are not following the manufacturer's instructions" -- is an excellent one.

There are lots of hurdles to improving the energy performance of our buildings, aren't there?


3.
Jan 13, 2018 12:05 PM ET

Edited Jan 13, 2018 12:14 PM ET.

My point is
by Walter Ahlgrim

My point is I can see both sides of this question.

The drywall manufactures have no economic incentive to change their reconditions as the change is unlikely to increase product sales any change adds risk however slightly. Take on risk for no benefit is the definition of a bad business decision.

Also I want people to see this question as a technical issue while they are planning stages and be prepared to deal with the type of push back I encountered. When I was planning I did not foresee attic insulation depth as a technical problem. I was thinking of it as solely a cost/ benefit decision when the technical push back came I was not prepared and I folded.

From a return on investment point of view R61 is the place I wanted to get to.

With some forethought I may have chosen a different insulation sub or been willing to sign off on ceiling liability.

Walt


4.
Jan 13, 2018 12:37 PM ET

A waiver
by Malcolm Taylor

A waiver by the insulator seems quite reasonable. They aren't responsible for the structural integrity of the materials they work around. Tile installers do the same if they aren't comfortable with the span or depth of the subfloor. The building industry quite reasonably works on assumptions about common practices. If we are going to deviate from them, the onus is on us to make sure all the conditions for success are there.


5.
Jan 13, 2018 2:01 PM ET

Just gotta say...
by Dana Dorsett

That first picture sure looks like a "less than picture-perfect" installation, with lots of dunes & dips. Most pros would rake it out flat, and have multiple paper depth gauges to refer to.

Or perhaps that's a work in progress- there appears to be depth markings on the king pins of the trusses varying from 2" to 12" above the existing cellulose levels in that attic.


6.
Jan 14, 2018 3:49 PM ET

Edited Jan 14, 2018 3:51 PM ET.

water vapor absorption a problem or an advantage of cellulose?
by Robert Opaluch

The lack of documented failures seems to indicate that water vapor absorption by cellulose isn't a problem.

An air or vapor barrier sheet product might add to the structural support for insulation above, in addition to strapping.

A problem might occur when a roof leak or wind-driven rain puts water into the attic and the cellulose gets heavier from water absorption. Plus water can damage the drywall and reduces its structural strength to resist the heavier cellulose. Any common type of loose fill insulation wouldn't stop drywall from getting damaged, but cellulose might be worse than lighter non-hygroscopic insulation (e.g., fiberglass)? Or cellulose might be better in cases with minimal water intrusion, since it would absorb moisture rather than pass the moisture to the drywall below? Or maybe be more likely to wick moisture to air above to dry out faster??

Just curious...how much water vapor could be absorbed by cellulose, and how heavy could the cellulose become with a higher percent of water content? Assume this would be more likely in summertime with more content moisture in the air, when air is reaching its dew point?


7.
Jan 14, 2018 5:20 PM ET

Definitely not a problem- especially in attics. @ Robert Opaluch
by Dana Dorsett

Even damp-sprayed cellulose is only ~40% moisture content by weight when applied, and drops back to ~10-15% m.c. within a couple of months. Even under extreme air conditioning with 68F ceiling gypsum in a 65F room temperature when outdoor dew points are in the mid-70s the moisture content won't go over 15%. They typical density numbers for dense packed walls assume ~10% m.c., but the actual density will vary a bit by season as water comes and goes.

Moisture saturation of the cellulose is more likely in wall assemblies in cold climates, where the cool side of the cellulose dwells WELL below the dew point of the conditioned space air for weeks and months at a time. Air leaks to the interior, and low vapor retardency on the exterior limiting the dry-through rates can theoretically get you there in a zone 6 or higher climate, but most instances of wet cellulose are due to bulk water leaks.

Small roof leaks can sometimes be masked by deep cellulose fill for quite awhile before the capacity of the cellulose is exceeded and it begins to seep through the ceiling gypsum.

A short sheet about cellulose & moisture from (the now defunct) National Fiber can be found here:


8.
Jan 15, 2018 5:41 AM ET

Response to Robert Opaluch (Comment #6)
by Martin Holladay

Robert,
I agree with Dana's analysis.

You wrote, "A problem might occur when a roof leak or wind-driven rain puts water into the attic and the cellulose gets heavier from water absorption." That's true -- but any ceiling can fail when faced with a roof leak, regardless of the type of insulation installed or the thickness of the insulation.


9.
Jan 15, 2018 3:08 PM ET

Edited Jan 15, 2018 3:08 PM ET.

Retrofittable belt & suspenders?
by Brian Bailey

For those that want to steer clear of this issue in an abundance of caution (or who have contractors who demand it), can some sort of decking be applied to the top of ceiling joists to support the load?

I can understand why subfloor or similar material would be undesirable from a moisture perspective, but what about a series of 1X4 strips with, say, 2" gaps between each pair? This would make a "breathable" support surface, with the side benefit of allowing future occupants to walk around in deep cellulose without fear of punching a foot through the drywall. Is there any reason why this can't or shouldn't be done?


10.
Jan 15, 2018 3:26 PM ET

Response to Brian Bailey
by Martin Holladay

Brian,
The space between the ceiling joists usually contains insulation, so your suggested 1x4s would divide the insulation depth into two sections -- below the subfloor and above the subfloor. There might be differential settling and air gaps with your method.

That's why I prefer the method suggested in my article (for worry-warts) -- "to install 1x3 or 1x4 strapping, 16 inches on center, on the underside of your ceiling joists before installing the drywall."